MCB MCCB Selection Chart & Calculator | Motor Breaker Sizing Guide

MCB MCCB Selection Calculator | Motor Breaker Sizing Chart | EI Engineer

MCB / MCCB Selection Master Calculator

Complete breaker sizing tool with FLC calculation, cable coordination, trip curve selection & PDF report download

Motor Protection Lighting Load Heater / Welding PDF Download

Breaker Selection Input / Breaker Input

Calculation Results / Results

Recommended Protection / Suggested Breaker
--
--
  • Full Load Current (FLC) -- A
  • Starting / Inrush Current -- A
  • Safety Factor Applied --
  • Calculated Rating -- A
  • Standard Rating Selected -- A
  • Breaking Capacity (Icu) -- kA
  • Trip Curve Type --
  • Selection Status --

Cable Sizing / Cable size

Minimum Required --
Recommended Size --
Voltage Drop --

Cable derating ambient & grouping ke liye already included.

Download Report / PDF

Complete calculation report with formulas download karein.

Quick Tip

Motor load ke liye hamesha starting current check karo. Type D curve DOL motor ke liye best hai.

Formulas Used / Calculation Formula

FLC = (P × 1000) / (√3 × V × PF × Î·)
Variables: P = Power in kW | V = Voltage (V) | PF = Power Factor | η = Efficiency
3-Phase: √3 (1.732) se multiply karte hain
1-Phase: Sirf V se divide karte hain, √3 nahi lagta
Starting Current: DOL mein 6x FLC, Star-Delta mein 2x, VFD mein 1.2x

Safety Guidelines / Safety Tips

  • MCB sirf overcurrent & short-circuit protection ke liye — overload ke liye OLR lagao
  • Motor ke liye Type C (5-10x) ya Type D (10-20x) trip curve use karo
  • Lighting ke liye Type B (3-5x) kaafi hai
  • MCCB 100A se upar ke load ke liye — thermal & magnetic dono setting adjustable hoti hai
  • Cable size hamesha breaker rating se zyada hona chahiye
  • Industrial panel mein 10kA minimum breaking capacity rakho

MCB Trip Curve Comparison Chart

Type Instantaneous Trip Best For Applications Starting Current
Type B 3 - 5 × In Residential / Light Commercial Lighting, computers, TV, fans Low inrush
Type C 5 - 10 × In Commercial / Small Industrial Motors up to 5kW, AC, pumps, lifts Moderate inrush
Type D 10 - 20 × In Industrial / Heavy Motor Big motors >5kW, compressors, cranes High inrush
MCCB Adjustable Main Distribution / Panel DB incomer, main supply, 100A+ loads Variable

Standard MCB & MCCB Ratings (A)

MCB Ratings (A) MCCB Ratings (A) Typical Application
6, 10, 16, 20, 25100, 125, 160Lighting, small appliances, sub-main
32, 40, 50, 63200, 250, 315Motors 1-15kW, AC units, pumps
80, 100400, 630, 800Main DB, big motors, distribution
-1000, 1250, 1600+Main incomer, LT panel, substation

Quick Unit Converter / Unit Conversion

1 HP = 0.746 kW
Horsepower to Kilowatt
1 kW = 1.36 HP
Kilowatt to Horsepower
kW = kVA × PF
kVA to kW (PF needed)
1 kW = 1000 W
Watt Conversion

Live Converter / Quick Convert

HP = kW
kVA × 0.85 = kW

Frequently Asked Questions / Common Questions

Q1: MCB aur MCCB mein kya farq hai?
MCB (Miniature Circuit Breaker): 0.5A se 100A tak ka load handle karta hai. Ghar aur chhote commercial setup mein use hota hai. Fixed thermal-magnetic setting hoti hai.

MCCB (Molded Case Circuit Breaker): 100A se 2500A tak ka load. Industrial panels, main distribution boards mein use hota hai. Adjustable thermal & magnetic dono setting hoti hai — trip current ko precisely set kar sakte ho.

Short mein: 100A se neeche = MCB, 100A se upar = MCCB.
Q2: Motor ke liye Type C ya Type D kaunsa MCB best hai?
Type C (5-10x FLC): Chhote motors ke liye — jaise 1HP se 5HP tak, jahan starting current zyada nahi hai. Agar motor DOL se start ho rahi hai aur 5kW se chhoti hai, Type C kaafi hai.

Type D (10-20x FLC): Bade motors, compressors, cranes, pumps ke liye. DOL starting mein 6-8x current hoti hai, Type D isko tolerate karta hai bina trip kiye.

Rule: Motor > 5kW + DOL = Type D. Motor < 5kW ya Star-Delta/VFD = Type C.
Q3: MCB ka breaking capacity (kA) kya hota hai aur kitna hona chahiye?
Breaking Capacity (Icu): Short-circuit current ki maximum value jo MCB safely break kar sakta hai bina damage ke. Agar panel mein fault current 10kA hai aur MCB ki capacity 6kA hai — toh MCB blast ho sakta hai!

Recommended:
  • Residential: 6kA kaafi hai
  • Commercial small: 10kA
  • Industrial / Factory: 25kA se 50kA
  • Main LT Panel: 65kA+ (fault current calculation ke baad)
Q4: Breaker rating direct motor HP se kaise nikaalein bina calculation ke?
Quick Thumb Rule for 3-Phase Motors:
  • 1 HP motor → 2A FLC → 6A MCB Type C
  • 3 HP motor → 4.5A → 10A MCB Type C
  • 5 HP motor → 7.5A → 16A MCB Type C/D
  • 7.5 HP motor → 11A → 20A MCB Type D
  • 10 HP motor → 14A → 25A MCB Type D
  • 15 HP motor → 21A → 32A MCB Type D
  • 20 HP motor → 28A → 40A MCCB
  • 30 HP motor → 42A → 63A MCCB
  • 50 HP motor → 70A → 100A MCCB
Formula shortcut: 3-Phase FLC ≈ HP × 1.4 (approximate for quick estimate)
Q5: Cable size aur breaker ka relation kya hai? Breaker bada aur cable chhoti kyun nahi chahiye?
Principle: Breaker ka kaam hai overload hone pe circuit ko kaatna. Agar breaker 63A ka hai aur cable sirf 4mm² (27A capacity) ki hai — toh 40A jaane pe cable garam hoke fire laga degi, breaker trip nahi hoga!

Rule of Coordination:
  • Cable Current Capacity > Breaker Rating > Load Current
  • Always: Cable size breaker se bada hona chahiye
Example: 32A breaker ke liye minimum 10mm² cable (50A capacity) recommended hai. 6mm² (36A) sirf borderline hai.
Q6: Voltage drop ka calculation kyun dikhaya hai aur maximum kitna allowed hai?
Voltage Drop: Jab current lambe cable se jaata hai toh resistance ki wajah se voltage kam ho jaata hai. Motor pe proper voltage nahi milegi toh:
  • Starting torque kam hoga — motor load se start nahi hogi
  • Motor garam hogi — insulation damage hoga
  • Efficiency gir jayegi — bill zyada aayega
IS Standard (IS 13252):
  • Lighting circuits: Max 3% voltage drop allowed
  • Power / Motor circuits: Max 5% voltage drop allowed
  • Main distribution: Max 2.5%
Q7: MCB ke saath OLR (Overload Relay) kyun lagate hain?
MCB: Short-circuit (instant 1000A+) aur thoda overload (1.13x to 1.45x) handle karta hai. Lekin motor ki winding 110% se zyada load pe slowly heat hokar jal sakti hai — MCB isko immediate detect nahi karta.

OLR (Overload Relay): Sirf overload ke liye bana hai. Motor current continuously monitor karta hai. Agar current set value se zyada jaati hai (jaise 105% ya 120%) — toh contactor ko trip kar deta hai.

Final Protection Setup for Motor:
  • MCCB/MCB: Short-circuit + moderate overload
  • Contactor: Switching control
  • OLR: Thermal overload protection
  • SPD: Surge protection (optional)
Q8: Star-Delta starter ke liye breaker kaise select karein? 3 breakers lagte hain na?
Yes! Star-Delta mein 3 contactors hain: Main, Star, aur Delta. Breaker sirf ek incoming MCCB/MCB lagta hai jo pura circuit protect kare.

Breaker Selection for Star-Delta:
  • Star-Delta mein starting current only 2x FLC hoti hai (vs 6x in DOL)
  • Isliye Type C breaker kaafi hai, Type D ki zaroorat kam hai
  • Breaker rating = 1.25 × Motor FLC
Example: 15kW, 3-Phase motor
FLC = 28A → Breaker = 32A or 40A Type C MCCB
Cable = 16mm² (68A capacity) minimum
Q9: 1-Phase MCB selection ka formula alag hai?
Haan, 1-Phase mein √3 (1.732) nahi lagta!

1-Phase Formula:
Current (A) = Power (W) / Voltage (V)

Example: 2kW, Single Phase geyser
Current = 2000W / 230V = 8.7A
Safety factor 1.25x → 10.8A
Recommended: 16A Type B MCB (next standard size)

Common 1-Phase Loads:
  • Geyser 2kW → 16A MCB
  • AC 1.5 Ton → 10A-16A Type C
  • Refrigerator → 6A Type B
  • Washing machine → 10A Type C
  • Home main (3kW total) → 32A/40A MCB
Q10: Generator ke output breaker ka size kaise calculate karein?
Generator Breaker Formula:
Current = kVA / (√3 × V) for 3-Phase
Current = kVA / V for 1-Phase

Example: 62.5 kVA, 3-Phase Generator
Current = 62500 / (1.732 × 415) = 87A
Safety factor 1.2x → 104A
Recommended: 125A MCCB (next standard)
Breaking capacity: Minimum 25kA

Tips:
  • Generator breaker hamesha 1.25x rated current se zyada ka ho
  • AVR failure pe overvoltage protection bhi rakho
  • Earth leakage protection (ELCB) must hai DG set ke liye

Cable Current Capacity Reference (PVC Insulated)

Cable Size (mm²) 1-Phase Current (A) 3-Phase Current (A) Motor Capacity (Approx)
1.51513Up to 1 HP
2.52018Up to 2 HP
42724Up to 3 HP
63632Up to 5 HP
105045Up to 7.5 HP
166860Up to 15 HP
259180Up to 20 HP
35115100Up to 25 HP
50145125Up to 40 HP
70185160Up to 50 HP
95225195Up to 60 HP
120260225Up to 75 HP
150300260Up to 100 HP
185345300Up to 125 HP
240410355Up to 150 HP

Values are approximate for PVC insulated copper cable at 35°C ambient. For armoured / XLPE cables, capacity 15-20% higher. Always refer to manufacturer catalogue for exact values.